b. Wire:

(1) Wire gage: 6.
(2) Minimum width: 7/8 in. (22 mm).
(3) Fabrication: Wire looped and closed.


6. Rigid anchors for intersecting bearing walls:

a. Dimensions: 1 1/2 in. (38 mm) wide by 1/4 in. (6.4 mm) thick by minimum 24 in. (610 mm) long.
b. Fabrication: Turn up ends minimum 2 in. (51 mm) or provide cross pins.


7. Wire ties for high-life grout reinforced brick masonry:

a. Minimum gage: 9.
b. Fabrication:
(1) Bend into stirrups 4 in. (102 mm) wide and 2 in. (51 mm) shorter than overall wall thickness.
(2) Form so that tie ends meet in center of one embedded end of stirrup.


2.04 CLEANING AGENTS:

A. Do not use cleaning agent other than water on brick, except with concurrent of Architect/Engineer.


B. Acceptable cleaner for dark brick:


C. Acceptable cleaner for light colored brick:


2.04.B Specify cleaner recommended by brick manufacturer.


2.04.C Proper cleaning agent is more critical for light colored brick.