Masonry Magazine July 2002 Page. 28

Masonry Magazine July 2002 Page. 28

Masonry Magazine July 2002 Page. 28
Prevention
Step right this way continued from page 23

ORIGINALLY, Section 1926.451(a)(4) required guardrails on all open sides and ends of a scaffold platform, but it didn't specify how far away a scaffold platform may be from a building before the side facing the building is considered to be an "open side." OSHA's existing scaffold rule has often been interpreted to mean that no open space is allowed. However, zero clearance during all phases of construction is not feasible.

A 14-inch limit was proposed in paragraph (b)(4) recognizing that during construction, the face of the wall being built often moves out toward the scaffold. There must be sufficient space at the beginning of work to allow for the installation of masonry units, ledges, facings and other architectural or structural additions. The spacing must be allowed for from the start, because it is not practical to move large scaffolds away from the wall as construction progresses outward.

When the initial set back distance must be more than 14 inches, the platform can often still be kept within 14 inches of the building by the use of side brackets or extensions on supported scaffolds, and by angulated roping, static lines, or equivalent means on suspension scaffolds.

While on the subject of scaffolds, paragraph (b)(9) provides that wood platforms shall not be covered with opaque finishes, except that platform edges may be covered or marked for purposes of identification. This paragraph is intended to ensure that structural defects in platforms are not covered from view by the use of an opaque coating or finish. Hairline cracks can significantly reduce the strength of a wood member, so early detection of structural defects is important. Opaque finishes can cover such cracks and make them difficult to discover. The edges of platform units are exceptions to this rule to allow identification marks, grading marks, or other similar type of marks to be placed on the unit edges.

Guidelines and policies

ALL CONTRACTORS, large and small, need to have written policy and procedure manuals for their workers. Not only does this provide a place for reference to safety rules so all can abide by them, it protects the contractor from many liability issues. "Rules is rules" may be the rule, but if you don't tell your crews what the rules are, how can they follow them?

Here are some guidelines that might make up sections of your company safety manual. They are offered as a starting point, not an ending point. They specify alternative procedures for protecting employees.

These procedures are:
Trained Workers Only. Only trained workers shall be allowed to work on the top of the foundation wall, and only as necessary to complete the construction of the wall.

Adequate Support. All formwork shall be adequately supported before any worker may work on top.

Bad Weather. When adverse weather (such as high winds, rain, snow or sleet) creates a hazardous condition, operations shall be suspended until the hazardous condition no longer exists. No one should be allowed on scaffolding covered with ice except for the purpose of removing the ice.

Staging of Materials/Equipment. Materials and equipment for the work shall be conveniently located to the workers. Reaching over or under the edges is prohibited without adequate fall arrest or protection systems in place.

Impalement Hazards. Materials and other objects which could pose impalement hazards shall be kept out of the area below where workers are working or shall be properly guarded. Ends of all protruding metal, lumber or plastic must be guarded. Mushroom caps are suitable for anchor bolts, rebars, and other objects located on the same surface as the workers. If workers are on an upper level above the protruding materials, mushroom caps are inadequate protection and 2x lumber must be used to cover all protruding objects.

Whenever a masonry wall is being constructed, a Limited Access Zone and a Controlled Access Zone shall be established prior to the start of construction. Limited Access Zone means an area along the unscaffolded side of the wall, which must be barricaded to limit access. The builder's competent person and the mason contractor's competent person must ensure that the Limited Access Zone is clearly marked and controlled by the mason contractor.

The Limited Access Zone (LAZ) must meet the following requirements:
* Entry shall be restricted to the mason contractor's employees (or subcontractor's employees) who are actively constructing the masonry wall.
* It must be protected either through warning tapes, ropes, wires or chains. The entryway must have a warning sign posted.

Bigger Profits

EaCo Chem
800-313-8505/www.eacochem.com
Come more from using this...
NMD 80
The New Standard of Excellence in
New Masonry Detergent
Cleans All Masonry
...than from using this...
highly
Better, Safer, Faster and it is Profitable
26 Masonry
July 2002
www.masonryshowcase.com


Masonry Magazine December 2012 Page. 45
December 2012

WORLD OF CONCRETE

REGISTER NOW; RECEIVE A FREE HAT!
The first 25 people to register this month using source code MCAA will receive a free MCAA Max Hat (valued at $15.00)! The MCAA Max Hat features a 3D MCAA logo embroidered on front with a

Masonry Magazine December 2012 Page. 46
December 2012

Index to Advertisers

AIRPLACO EQUIPMENT
888.349.2950
www.airplace.com
RS #296

KRANDO METAL PRODUCTS, INC.
610.543.4311
www.krando.com
RS #191

REECHCRAFT
888.600.6060
www.reechcraft.com
RS #3

Masonry Magazine December 2012 Page. 47
December 2012

AMERIMIX
MORTARS GROUTS STUCCOS

Why Amerimix Preblended Products?

576

The choice is CLEAR:

Consistency

Labor reduction

Enhanced productivity

ASTM - pretested to ASTM specifications

Masonry Magazine December 2012 Page. 48
December 2012

MASON MIX
Type S Mortar
QUIKRETE
www.quikrete.com
800-282-5828

MASON MIX
Type 5 Mortar
COMMERCIAL GRADE
QUIKRETE

Our mortar mix on Vail's Solaris was so consistent, every bag was like the next. And the next